10-120KVA


    Technical Features:
    ● High-speed DSP digital control
    ● Full-bridge invertert control techonology, providing secure power supply in the event of three phase 100% unbalanced loads
    ● Multi-string PV connected
    ● Inbuilt AC rectifier and MPPT control modules, configured battery parameters by operating interface, self-regulation for charging voltage and current
    ● Hot-swap MPPT modules for easy maintenance and power expansion
    ● Auto access MPP tracking states, be most probable to use PV energy in priority
    ● Intelligent AC and PV complementation power supply function to extend the battery life.
    ● Using multicore control technology and auto MPP trackers, auto-start AC rectifier enable PV and AC source to supply power to the loads at the same time in the event of insufficient PV, which reduces battery discharge times and entend the battery life.
    ● Intelligent staggering power consumption function
    ● Standard RS232, RS485 and optional SNMP communication port
    ● Multiple remote control: startup, shutdown, abnormal clearance, EPO, battery test and remote alarm port
    ● Staggering energy storage and power generation

    Technical specifications

    MODEL OG-10 KVA OG-20 KVA OG-30 KVA OG-40 KVA OG-60 KVA OG-80 KVA OG-100 KVA OG-120 KVA
    Rated power 9 KW 18 KW 27 KW 36 KW 54 KW 72 KW 90 KW 108 KW
    Rated current 15 A 30 A 45 A 60 A 91 A 120 A 162 A 182 A
    Output power factor 0.9
    Rated input voltage 380 V ± 20%
    Rated output voltage 380 V ± 1%
    Battery voltage 360 Vdc
    Number of battery 12 V * 30 pcs / 2 V * 180 pcs
    Operating mode AC and PV complementation
    PV INPUT
    Max. voltage (Voc) 750 Vdc
    Optimum operating voltage (Vmp) 450 ~ 550 Vdc
    Max. conversion efficiency ≥ 98%
    Floating charge voltage (25) 414 V ± 1%
    Equalizing charge voltage (25) 428 V ± 1%
    MPPT Max. current 60 A 120 A 180 A 240 A 360 A
    Max. PV power 25 KW 2 * 25 KW 3 * 25 KW 4 * 25 KW 6 * 25 KW
    Number of PV input 1 2 + 1 (reserve) 3 + 1 (reserve) 4 + 2 (reserve) 6 + 2 (reserve)
    MPPT modules 1 2 + 1 (reserve) 3 + 1 (reserve) 4 + 2 (reserve) 6 + 2 (reserve)
    AC RECTIFIER
    Input voltage range 380 V ± 20% three-phase
    Rated frequency 50 Hz / 60 Hz ± 5 Hz (settable)
    Power factor 0.8
    Floating charge voltage (25) 410 V ± 1%
    Equalizing charge voltage (25) 415 V ± 1%
    Max. charging current 12 A 25 A 38 A 50 A 75 A 167 A 208 A 250 A
    INVERTER
    Inverter voltage 380 Vac three-phase + N+G
    Phase voltage 220 / 230 / 240 Vac (settable)
    Output voltage precision ± 1%
    Transient voltage range ± 5%
    Transient recovery time 20 ms
    Rated frequency 50 Hz / 60 Hz ± 1 Hz (settable)
    Frequency tracking range 50 Hz / 60 Hz ± 3 Hz
    Peak factor 3:01
    Waveform Sinusoidal
    Waveform distortion ≤ 3% (linear load)
    Voltage unbalance ± 3% (100% unbalanced load)
    Overload ≥ 105% ~ 110% for 1 h;
    ≥ 110% ~ 125% for 10 mins;
    ≥ 125% ~ 150% for 1 min;
    ≥ 150% shut down in 10 s;
    ≥ 200% shut down immediately;
    Short circuit Current-limiting, shut down immediately until the user start up
    Max. efficiency ≥ 90% ≥ 91% ≥ 92% ≥ 93%
    BYPASS
    Rated voltage 380 Vac three-phase + N+G
    Voltage range ± 20%
    Rated frequency 50 Hz / 60 Hz ± 5 Hz
    Max. current 19 A 38 A 57 A 76 A 114 A 152 A 190 A 228 A
    BATTERIES MANAGEMENT
    EOD voltage settings 1.58 V ~ 1.83 V (settable), 1.75 (default)

    Staggering DOD 

    (Depth of Discharge) settings

    1.85 V ~ 2.1 V (settable), 1.89 (default)
    Charging current settings Factory default 0.15 C10; 0.07 ~ 0.3 C10 (settable)
    Battery management Auto-transfer between equalizing charge and floating charge; Auto- temperature compensation of batteries
    TRANSFER TIME
    Inverter – Bypass 0 ms
    Bypass – Inverter 0 ms
    COMMUNICATIONS
    Remote control Inverter startup, shutdown, abnormal clearance, EPO, battery self-test
    Communication interface RS232, RS485, SNMP (optional)
    Dry contacts output  

    Bypass input abnormal, rectifier input abnormal, system fault, system alarm, low battery,

     output overload, fan fault, generator ON / OFF

    OTHERS
    Operating temperature 0 ~ 40
    Max. relative humidity 90% (non-condensing)
    Max. altitude 1000 m at rated power (derating 1% for each additional 100 m); Max. 4000 m
    Noise level at 1 m ≤ 65 dB (varies with loads and temperature)
    IP rating IP20
    Dimensions (W × D × H) (mm) 450 × 840 × 1100 600 × 700 × 1750 960 × 800 × 1700

    Packaged dimensions 

    (W × D × H) (mm)

    530 × 920 × 1140 690 × 790 × 1850 1040 × 890 × 1750
    Weight (kg) 230 245 380 430 515 760 800 860